BDI-2002 series_Weighing Indicator & Controller
-
Analog Input and A/C Conversion::
-
Type:BDI-2002
-
Input Sensitivity:0.8µ V/D
-
ZERO Adjustment Range:0 ~ 20 mV
-
Max. Resolution:1/16,000 (Max. 1/60,000 depending on load cell quality & performance)
-
Main. Display (Green Tube):7-segment, 7-digit display, VFD screen with a 13mm character size, displays the weight.
-
Minimum Division:x1, x2, x5,x10, x20, x50
-
Maximum Display:+800450
-
Load Cell Excitation:DC 10V ± 1%, 230mA, Remote Sensing. Can be connected up to 8-(350ΩLoad Cells)
-
Non-Linearity:0.01% F.S
-
A/D Conversion Method:ΔΣ
-
A/D Resolution:1/1,000,000
-
A/D Conversion Rate:Approx 120 Times/ Sec.
-
Max. Load Cell Input Voltage:32mV
-
ZERO Temperature Comp.:± (10.2µV + 0.001% of Dead Load) /˚C TYP
-
SPAN Temperature Comp.:± 0.001% ˚C TYP
-
General::
-
Type:BDI-2002
-
Power Requirements:AC 220V ± 10%, 50/60 Hz Approx. 17VA
-
Net weight:Approx. 3.2kg (7.054 LB)
-
Operation Temperature:- 10˚ C ~ 45˚ C
-
Maximum Humidity:85% (non-condensing)
-
Physical Dimemsions:240 (D) X 190 (W) X 104 (H) mm
-
Standard::
-
Current Loop:20mA
-
Options::
-
OP-01:I/O Interface
-
OP-02:Sesial Interface RS-232 or RS-422/485
-
OP-03:Printer Interface (include Date and time)
-
Op-04:Parallel BCD Output
-
OP-05:Analog Output 4~20mV
-
OP-06:Analog Output 0~10V
Description
OPTION: CONTROL 1/0. RS232/422/485.
PRINTER INTERFACE. BCD. 4~20mA. 0~10V.
Breakthrough high display resolution.
Batching control (feeding & loss-in-weight)
120 Times/sec A/D conversion rate.
Fully digital calibration
Compact size
BDI-2002 Weighing Indicator & Controller Features:
* 1/16,000 display resolution (Max. 1/60,000 depending on load cell quality & Performance)
* Internal Resolution 1,000,000 A/D Conversion rate 120 time/ Sec.
* Watchdog virtually eliminates malfunctions that associated with computerized equipment or software failure.
* Full Digital Calibration makes setting ZERO and SPAN Calibration an easy task.
* Drives up to 8 parallel connecting load cells. (350Ω)
* 8k bytes SRAM with Li-battery backup. Information will not disappear even power failure.
* The setting of function and weighing parameters are all stored in the EEPROM, with storage duration over 40 years.
* Important values and parameters can have storage backup.
* Users can adjust the intensity of digits to avoid mechanical vibration that caused by external environments to achieve high-speed and accurate measurement.
Set point codes can store up to 100 sets of: Final, SP1, SP2, FREE FALL, HI, LO.
Automatic Free Fall compensation provides closer tolerance and precise weighing.
8 Set of control input: ZERO Input, TARE Input, TARE reset, Start batch, Abort batch, Print Accumulater,
Print Input, Clear ACC. & COUNT.
8 Set of control output: ZERO Band output, SP1 output, SP2 output, (Final-Free Fall) output, HI output, LO output, Final output, MD/Error output.
5 batching ,odes: Customer Programmed Control Made: Normal Batching. Customer Programmed Control
Model: Loss-in-weight batching, Built-in Automatic Program Mode: Normal batching, Built-in-Automatic Program
Mode: Loss-in-weight Batching, Multiple-Ingredient Batching.
Standard Serial Output (20mA Current Loop) for remote display.
Optional printer interface can automatically print or output data includes, time point code, serial number weight, and unti